Mechanical Supplies
Fiberglass Isolators
About
- Kinetics moulded inorganic fiberglass isolation, Model FH hangers and Model KIP pads, coated and colour-coded by load range, giving low-frequency isolation with a very low profile and no exposed steel to corrode. KIP pads are selected by density so different load ranges under one slab still share a constant natural frequency.
Application
Used under floating concrete floors, generator and transformer bases, and as jack-up pads under plant where headroom will not take a spring mount. Because the pad is selected for a target natural frequency rather than a fixed deflection, a single floating slab carrying very unevenly distributed load can still be tuned to behave as one mass.
Standards & Reference 4 cited
ASTM E90
The laboratory measurement of airborne sound transmission loss: the raw data a partition's acoustic rating is derived from.
ASTM E492
Impact sound transmission: the footfall equivalent of ASTM E90, summarised as an Impact Insulation Class.
ASTM E84
Surface burning characteristics: the flame spread index and smoke developed index a material is classified by. Class A is the usual requirement in an occupied building.
ASHRAE Handbook, HVAC Applications Ch. 49
The noise and vibration control chapter of the ASHRAE Applications Handbook: the reference isolator selection and deflection tables are drawn from.
Request for quotation
Get a price for this item
Send the quantity and the project. Our sales engineers reply with a quotation, usually within one working day.
More in this line
Vibration Isolation, Seismic & Riser
4 products
View All