Mechanical Supplies
Suspended Vibration Isolation
About
- Kinetics hanger isolators in three families: Model SFH (a laterally stable steel spring in series with a precompressed moulded fiberglass insert), Model FH (moulded inorganic fiberglass pad on a steel load transfer plate) and Model RH (neoprene). SFH covers deflections of 1.04"-2.20" (26-56 mm) and 4.05"-4.75" (104-112 mm) at capacities from 35 to 3,850 lb
- all three carry a 500% overload without failure and allow the support rod to swing through a 30° arc.
Application
Used on suspended fan coil units, inline fans, ductwork close to a fan discharge, and the first three hangers of any pipe run leaving a pump. FH is the choice in high-temperature ceiling voids where a spring is not wanted. The commonest field failure is a hanger rod touching the box: the 30° arc exists precisely to prevent that metal-to-metal short circuit, because once it happens the isolator is rigid and every reading taken afterwards measures the structure.
Standards & Reference 4 cited
ASHRAE Handbook, HVAC Applications Ch. 49
The noise and vibration control chapter of the ASHRAE Applications Handbook: the reference isolator selection and deflection tables are drawn from.
ASCE 7 Ch. 13
The seismic design requirements for nonstructural components: the chapter that decides how mechanical plant must be restrained against earthquake.
ICC-ES AC156
The acceptance criteria for seismic certification by shake-table testing: how equipment earns a certificate rather than a calculation.
SMACNA Seismic Restraint Manual
Guidelines for bracing mechanical services against earthquake loads: the practical companion to the code requirement in ASCE 7.
Request for quotation
Get a price for this item
Send the quantity and the project. Our sales engineers reply with a quotation, usually within one working day.