Mechanical Supplies
Wall-mounted axial fans
About
- Wall-mounted axial fans with a plate or ring-mounted impeller, available with fixed or automatic shutters and weather cowls. Simple, low-cost and easy to replace, with no ductwork resistance to overcome, the fan is selected at or near free delivery.
Application
Used for direct through-wall ventilation of workshops, warehouses, substations, generator rooms and plant rooms. Selection is limited by the physics: an axial fan loses volume rapidly against static pressure, so these suit free-discharge duties and become the wrong choice the moment ductwork, a sand trap louver or a filter is added in front of them.
Standards & Reference 5 cited
AMCA 210
The laboratory method for testing fan aerodynamic performance: airflow, pressure, power and efficiency. A fan curve that is not tested to this is not comparable with one that is.
AMCA 300
The reverberant room method for measuring the sound a fan emits. The source of the sound power figures used in an acoustic calculation.
ISO 5801
The international method for testing industrial fan performance using standardised airways. It is the ISO counterpart to AMCA 210.
IEC 60335-2-80
Safety requirements specific to fans, within the general standard for household and similar electrical appliances.
Also citedErP 327/2011
Documents
Request for quotation
Get a price for this item
Send the quantity and the project. Our sales engineers reply with a quotation, usually within one working day.
More in this line
Fans
12 products